  • Description
  • Technical data
  • PDF download

1, switch on, set panel on automatic position, the indicator lamp will be on, now procedure is waiting orders.

2, when lost outer-electricity; the procedure will star to work in 3 seconds.

3, when restarting please stop working for 8 seconds and prolong 1 second

4, the system will restart 3 times, and each time 15 seconds

5, if the system can not boot in 3 times it will shut down, and the light will be alarming.

6, the machine will switch over and generate electricity to export in 15 seconds after start,.

7, when outer-electricity come the machine will unload load in 2 second, work with empty-duty for 10 second, and shut down in 8 seconds.

8, switch to outer-electricity in 5 seconds after come to a complete stop.

9 , if the temperature of water or oil beyond the limit , the indicator lamp will be alarming ,and the machine will shut down automatically in 20 seconds.

10, while pressure of engine oil go too weak, the diesel engine will shut down by force , and the working state indicator lamp will be alarming.

11,if generator encounter trouble, the diesel engine will shut down by force, the indicator lamp of the working state glimmers and alarming.

12, working state indicator lamp, fault alarming forms.


trouble
alarming frequency of indicator lamp
last time
insufficient presser of engine oil
1
2
oil temperature beyond limit
2
2
water temperature beyond limit
3
2
generator matter
4
2
diesel engine do not boot
5
2
The diesel engine can’t stop working
6
2
 

Genset Model

Unit 

YD9

YD10

YD12

YD16

YD20

YD30

Standby Rating 

 kw

9

11

13.2

17.6

22

33

 KVA

12.1

13.8

16.5

22

27.5

41

Prime Rating

 kw 

8

10

12

16

20

30

 KVA

10

12.5

15

20

25

37.5

Controller

 

ATS

ATS

ATS

ATS

ATS

ATS

Engine 

Model

  

YD380

Y385

YD480

YD485

YSD490

Y4100

12h Power

 kw

10

11

13.2

15

21

27

Speed 

 rpm

1500

Fuel use

g/kw.h 

247

247

250.2

250.2

235

23.5

Closed water cooled/Electric starting

Alternator

TFW or STC or Leroy somer or STAMFORD or Marathon

Rated Output

 kw 

8.6

8.6

10

12

16

20

Rated Current

 A

15.5

15.5

18.1

21.6

28.9

36.1

Rated Voltage

 V

400/230

Fre

Hz 

50

Power Factor

COSφ 

0.8Lagging

Tech

3-phase,4-wire,Y type connection, Brushless, Automatic

Net Weight 

 kg

525

550

600

700

750

800

Package

 cm

120*60*110

130*65*120

150*73*125

 

 

 

 

Description

Automatic Transfer Switches (ATS). An ATS is a device that interfaces with a generator and the building's electrical system. It monitors the utility power and signals the generator to start if the utility power goes out of spec or drops out entirely (blackout). Backup power is now fed to the main utility panel or an emergency panel via the ATS.Automatic Mains Failre(AMF) detection with genset automatic starting-up/shut down,atuomatic load control(need ATS),automatic crank disconnecting,parameters display,monitoring,and protections.

ATS&AMF Features

Automatically controls the diesel to start and stop.

The controller provides the following analogue channels: three phases/wire generator voltage, three-phase load current, battery voltage, coolant temperature, oil pressure, generator speed, generator frequency, charge voltage, total run time.

The controller accepts four digital inputs: remote start, high coolant temperature, two configurable inputs.

Relay outputs are provided for LCD1, LCD2, LCD3, LCD4, three configurable outputs.

Custom digital inputs and relay outputs.

Automatically shuts down the diesel on fault condition.

Multiple diesel alarm channels are provided to monitor the following: under/over generator voltageload current overloadunder/over generator frequencylow oil pressurehigh coolant temperatureover speedcharge failure, low battery voltageemergency stopfail to start.

Multicolor and graphical icon LCD display.